Wet System
It is the first preferred system type in fire systems. In wet systems, pressurized water waits inside of pipe and immediately begins to be discharged with the operation of the relevant extinguishing equipment. The reason why this system is preferred in fire cabinet, hydrant and sprinkler systems is that it provides the opportunity to directly intervene in the fire without delay. The main control valve used in this system is called wet alarm valve system.
Dry System
It is the second most prefered used system after wet system. They are used for an alternative to wet systems where there is a risk of freezing (where the ambient temperature may fall below + 4°C) Different from wet systems, it waits in the compressed air or nitrogen inside of pipe instead of pressurized water and with the operation of the relevant extinguishing equipment. Firstly air or nitrogen is discharged and later water is observed to discharging. The main control valve used in this system is called dry alarm valve system.
Pre-Action System
They are the preferred systems in areas where valuable items (artworks, manuscripts, important document archives, etc.) are protected from water damage caused by incorrect activation. As in dry systems, pre-action systems also contain air or nitrogen inside of the pipe.
With the operation of the relevant extinguishing equipment, first the air or nitrogen in the line is discharged but the water isn’t allowed to discharging immediately. Meanwhile, a pre-fact is given by warning alarm devices on the main control valve. Confirmation is expected from other detection devices and allow the water discharging. In the event of a real fire, the extinguishing equipment will be disharged after detection devices will confirm the fire. In this way, the water will reach the discharge devices and extinguishing process will start. The main control valve used in this system is called pre-action alarm valve system.
Deluge System
These are systems in which water is discharged simultaneously from all extinguishing equipment connected to the same system using open-ended extinguishing equipment (nozzle, sprinkler without glass bulb, foam makers, etc.). In these systems, pipes and extinguishing equipments are connected to the main control valve (deluge valve). All pipes above the main control valve are empty and the main control valve is opened with the command from the detection system, and the fire is intervened with all extinguishing equipment at the same time. Generally in the design of special extinguishing systems preferable. The main control valve used in this system is called deluge alarm valve system.
Sprinkler Systems
Sprinkler systems are designed and installed to protect against loss of life and property in the event of a fire and consist of equipment such as sprinkler heads (sprinklers), valve groups, distribution pipes, pump group providing pressurized water.
Heat sensing element when one or more sprinkler heads are exposed to sufficient heat in the event of a fire (fusible link or glass bulb) becomes active and the pressurized water is distributed within a specific spray characteristic.
The activation temperature of the sprinkler thermal activation element is selected according to the ambient temperatures in which the sprinkler is used and they become active when this temperature is reached.
Protection areas can be 21m2, 12.1m2 and 9.3m2 depending on the hazard classes of the areas where they will be used. There are also special types of sprinklers with large protection areas.
Sprinkler systems are used in many areas such as car parks, shopping malls, high-rise buildings, workshops and storage areas.
System designs are made based on standards such as NFPA13, FMDS02-09, EN 12845 etc.
Fire Cabinet Systems
It means a fixed installed system to enable people to control and extinguish a small fire nearby.
Fire cabinet system consists of fixed units mounted on walls or inside cabinets and permanently connected to a water supply system.
Fire cabinets can be different according to their usage areas and material contents. These differences are determined according to the intended use and the appropriate cabinet type is selected.
According to Turkey Fire Protection Regulation 2015;
Workshops, warehouses, accommodation, health, gathering and education buildings with a total indoor area of more than 1000 m2,
in parking garages whose total area is larger than 600 m2,
In boiler rooms with a thermal capacity of more than 350 kW,
fire cabinet system is required.
Fire Hydrant Systems
Fire hydrant systems provide a pressurised water resource to firefighters’ hoses at inside and outside the building.
Generally, when it comes to hydrant system, the first thing that comes to mind is the outer field type fire hydrant systems surrounding the facility, but there are also systems used in the building, also called “Fire Hose Valve Systems”.
According to Turkey Fire Protection Regulation 2015;
It is mandatory to make fire hose valve system in buildings with any dimension more than 60m or a floor area of more than 1000m2.
It is compulsory to make outside type hydrant systems in facilities whose total base areas exceed 5000m2.
Hydrant system design flow must be at least 1900 l / min @ 7bar.
The distance between hydrants are 50m in high-risk areas, 100m in risky areas, 125m in medium-risk areas and 150m in low-risk areas.
Under normal conditions, hydrants are placed at an average distance of 5 to 15 meters from outside surface of buildings.
If the piping system providing water to the hydrant system is not designed as a ring system, the diameter of the smallest pipe that can be used should be 100mm and it should be determined according to the hydraulic calculation.
Water Mist Systems
Compared to the conventional sprinkler system, by separating the water into smaller droplets (500-1000µm on average), expanding the heat transfer surface of the droplets during extinguishing and evaporating these droplets in a shorter time (thanks to change of state, very serious energy absorption from the environment) the energy of the fire is reduced and a great cooling effect is provided.
In addition, water passing from the liquid phase to the gas phase (steam) during the process prevents the oxygen in the environment from directly reaching the flammable surface intensely and creates a suffocating effect.
At the same time, it can enter into closed systems and in this way it performs 3-D quenching.
Although it is categorized differently in European and American standards, the most common form is water mist systems according to operating pressures;
a) Low pressure,
b) Medium pressure,
c) High pressure water mist systems.
System designs are made based on standards such as NFPA750, FM5560, EN 14972, VDS CEA 4001 etc.